Coleman 3000 SERIES Spécifications Page 4

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 28
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 3
2
Specifications
Input:
• Voltage:24VAC(18-30VAC)
Output:
• Maximum:1ampmaximumloadperterminal
(4amptotalmaximumloadforallterminals)
Temperature Ranges:
• Temperature control range: 45°Fto90°F(7°Cto32°C)Accuracy:±1°F(±0.5°C)
• Differential range: 1°Fto3°F(0.5°Cto1.5°C)
System configurations:Multi-stageheatpump(two-stageheat,two-stagecool)
Terminations:R,C,E,Y1,Y2,O,B,G,L,W2
Second stage activation in heat mode:2°belowrststage(notadjustable)
Second stage activation in cool mode:2°aboverststage(notadjustable)
SET
ROOM
DIFF
Temperature
differentialsetting
Roomtemperature
Roomtemperature
setpoint
Package Contents/Tools Required
Package includes: SimpleComfort
®
2201non-programmablethermostatonbase,thermostatcover,wiringlabels,
screwsandwallanchors,Installation,OperationandApplicationGuide.
Tools required for installation:Drillwith3/16”bit,hammer,screwdriver.
Features/Benefits
• Multi-stageheating/coolingcontrol
• Multi-coloredLEDindicatorsforsystemstatus
• Zonesystemcompatibleasamasterthermostat
• Fahrenheitdisplayandoperationcanbechanged
toCelsius
• Adjustabletemperaturedifferential: 1°Fto3°F
(0.5°Cto1.5°C)
• Automaticheatingsystemshutdowniftemperature
exceeds90°F(32°C)
• 30-minutepowerinterruptionmemoryretention
• Resetbuttonfordifferentialtemperatureadjustment
• Independentsetpointsforheatandcool
Vue de la page 3
1 2 3 4 5 6 7 8 9 ... 27 28

Commentaires sur ces manuels

Pas de commentaire