INSTALLATION INSTRUCTIONS
DLAS MODELS
(No Coil Cabinet)
DGAT & DGAM MODELS
(With Built--In Coil Cabinet)
For Installation In:
1. Manufactured (Mobile) Homes
2. Recreational Vehicles & Park
Models
3. Modular Homes & Buildings
SEALED COMBUSTION
DOWNFLOW GAS FURNACES
Forced Draft with Direct Ignition (Hot Surface)
FURNACE SET--UP CHECK LIST
IMPORTANT: ONLY INDIVIDUALS HAVING PROVEN EXPERIENCE WITH THIS TYPE OF EQUIPMENT
SHOULD ATTEMPT TO PERFORM SET--UP.
- HAS ROOF JACK CROWN BEEN CORRECTLY
INSTALLED?
- HAS FURNACE GAS VALVE AND BURNER
ORIFI CE BEEN CORRECTLY CONVERTED
FOR L.P. GAS WHERE APPLICABLE?
- HAS FURNACE GAS VALVE BEEN DE--RATED
FOR ALTITUDES ABOVE 2000 FEET WHERE
APPLICABLE?
- IS GAS LINE OUTLET PRESSURE PROPERLY
SET FOR F UEL TYPE? (NATURAL GAS IS 3.5”
W.C.;L.P.IS10”W.C.)
- IS PRIMARY AIR PROPERLY ADJUSTED PER
INST ALLATION INSTRUCTIONS?
- IS CROSS--OVER DUCT INSTALLED PER
HOME BUILDER AND EVCON INSTALLATION
INSTRUCTIONS?
- HAS FURNACE BEEN OPERATED THROUGH
A COMPLETE HEATING CYCLE?
IMPORTANT: PROPER FURNACE SET--UP AND ADJUSTMENT IS THE RESPONSIBILITY OF THE
RETAILER/HOMEOWNER AND IS NOT COVERED UNDER WARRANTY.
Vue de la page 0
1 2 3 4 5 6 ... 27 28

Résumé du contenu

Page 1 - DOWNFLOW GAS FURNACES

INSTALLATION INSTRUCTIONSDLAS MODELS(No Coil Cabinet)DGAT & DGAM MODELS(With Built--In Coil Cabinet)For Installation In:1. Manufactured (Mobile) H

Page 2 - TABLE OF CONTENTS

10AIR DISTRIBUTION SYSTEMSFor proper air distribution, the supply duct system shall bedesigned so that the static pressure does not exceed thelisted s

Page 3

11ROOF JACKSOnly use the appropriate roof jack.See TABLE 4 & TABLE 5 for correct application.Do not exceed the maximum height as determined fromTA

Page 4 - LIST OF FIGURES

12TABLE 4 — DLAS Roof JacksRoof JackInstallation DimensionsModelNumber¡Adjustable Height4000--7121/C 75” to 86”These dimensions are4000--7141/C ** 83”

Page 5

13CEILING RINGSThe ceiling ring is to meet fire stop requirements. Acces-sory Ceiling Ring (P/N 7660--2841) may be used, (seeFigure 10) or the mobile

Page 6 - FURNACE SPECIFICATIONS

14DLAS SERIES FURNACESInstallation Procedure for DLAS FurnaceThe following steps are listed for installation of furnace andneed not be performed in th

Page 7 - INSTALLATION STANDARDS

15DGAT & DGAM SERIES FURNACESInstallation Procedure for DGAT & DGAMFurnacesThe following steps are listed for installation of furnace andneed

Page 8 - Clearance

16CONNECTING ROOF JACK TO FURNACEThe inner flue pipe must be present.It is mandatory that the combustion air pipe and fluepipe assembly be fully engag

Page 9

17IMPORTANTVENT SYSTEM INSTALLATION INSTRUCTIONSFAILURE TO FOLLOW ALL VENTING INSTRUCT--IONS CAN RESULT IN FIRE, ASPHYXIATION, OREXPLOSION.The vent sy

Page 10 - AIR DISTRIBUTION SYSTEMS

18ELECTRICAL WIRINGTO INSTALLER: INCOMING POWER MUST BE PO-LARIZED. OBSERVE COLOR CODING.DANGER-- SHOCK HAZARD --DISCONNECT ELECTRICAL POWER SUPPLY TO

Page 11 - ROOF JACKS

19THERMOSTAT WIRING FOR DGAT AND DGAM SERIESFigure17 -- Thermostat WiringWhiteGreenBlackRedBlend AirControl BoxCondensingUnitWall ThermostatFurnace Co

Page 12 - Figure 8 — DLAS Models

2TABLE OF CONTENTSGENERAL SPECIFICATIONS AND INSTRUCTIONS 5...FURNACE SPECIFICATIONS 6...I

Page 13 - DUCT CONNECTORS

20THERMOSTAT WIRING FOR DLAS (HEAT ONLY) SERIESWall Thermostat(Rear View)Furnace Control BoxFigure17a -- Thermostat Wiring for DLAS SeriesRWWhiteGreen

Page 14 - DLAS SERIES FURNACES

21WIRING DIAGRAMSFigure 18 -- DGAT Series Wiring DiagramWGRHYWallThermostat1 2 3 4 5 6 7 8 9UpperLimit SwitchLowerLimitSwitchCentrifugalSwitchCombusti

Page 15 - Furnaces

22WIRING DIAGRAMSFigure 19 -- DGAM Series Wiring DiagramBlend AirControl Box(If equipped)GRHYWallThermostat1 2 3456 78 9UpperLimitSwitchLowerLimitSwit

Page 16

23GAS PIPINGINSTALLATION AND CHECKING OF GAS LINEGas Supply piping must be sized in accordance with the rec-ommendations contained in “American Nation

Page 17 - IMPORTANT

24However, the amount of combustion air required will vary de-pending on altitude, actual BTU. content of the gas beingused, gas pressure, conversion

Page 18 - ELECTRICAL WIRING

25If Furnace Fails to Operate Properly1. Check setting of thermostat -- and position of HEAT/COOL switch if air conditioning is installed. If a set--b

Page 19

HIGH ALTITUDE DERATION CHART — DGAM, DGAT, DLAS SeriesNATURAL GAS56,000 — Input 70,000 — Input 75,000 — Input 90,000 — InputElevationOrificeDia.Drill

Page 20 - Furnace Control Box

27DGAM, DGAT & DLAS SERIESHSI Gas Downflow FurnaceRepair Parts List for:DGAM056BDE DGAT056BDE DLAS056BDE DGAT070BDE DGAM075BDE DGAT075BDE DLAS075B

Page 21 - WIRING DIAGRAMS

28DGAM, DGAT, & DLAS SERIESHSI GAS DOWN FLOW FURNACECODEUSED ONMODELNO.REQ.PARTNUMBERDESCRIPTION6 ALL 1 7990--401 Cover (Control Box)*7 ALL 1 7990

Page 22

3GAS PIPING 23...INSTALLATION AND CHECKING OF GAS LINE 23...Obse

Page 23 - GAS PIPING

4LIST OF FIGURESFigure 1 — Furnace Dimensions 5...TABLE 1 — Furnace Specifications 6...

Page 24

5GENERAL SPECIFICATIONS AND INSTRUCTIONSDGAT & DGAM SeriesDLAS Series60 1/2”76”19--1/2”9--3/4”23”24”10--5/8”19--1/2”9--3/4”23”24”10--5/8”15--- 7/8

Page 25 - FINAL PROCEDURE

6FURNACE SPECIFICATIONSTABLE 1 — Furnace SpecificationsDGAM — Automatic ignition — with Built --in Coil Cabinet — 4 Ton -- A/C ReadyModel No. Factory

Page 26 - PROPANE GAS

7INSTALLATION STANDARDSComply with Local CodesThe installer shall familiarize himself with and comply with alllocal codes and regulations which govern

Page 27 - HSI Gas Downflow Furnace

8RETURN AIR REQUIREMENTSCLOSET INSTALLATIONSFigure 3 — Closet to Door Clearance — 6” or greaterCLOSETFURNACEDOOR6” or greater —Closet to DoorClearance

Page 28 - Unitary Products Group

9SPECIAL CLOSET INSTALLATIONSFurnace to Closet Door Clearance — Greater th an 1 Inch and Less than 6 In ch esFigure 4 — Furnace to Closet Door Clearan